Sub-station Transformers
This type of transformer is used in sub stations to transfer
the incoming voltage to the next voltage level. It can
be system or auto transformer with two/three windings.
In general it is equipped with On load
tap changers and are connected to transmission
grids by bushings and cables.
The system/auto transformer is built
in core form. HV/LV windings are galvanically
separated for system transformer while they are
Auto connected for auto transformer.
|
|
Generator Transformers
This is a type of Power Transformer where the
LV winding is connected to the generator through
the bus duct and HV winding to the transmission system.
In addition to the features of Power Transformer, our
Generator Transformer is designed to withstand over voltage
caused by sudden load throw off from
the generator. It is built as a single or three phase
unit and located in power stations.
|
|
Unit Auxiliary Transformers (UAT)
The Unit Auxiliary Transformer is the Power Transformer
that provides power to the auxiliary equipment of a power
generating station during its normal operation. This transformer
is connected directly to the generator out-put by a tap-off
of the isolated phase bus duct and thus becomes
cheapest source of power to the generating station.
It is generally a three-winding transformer
i.e. one primary and two separate secondary windings.
Primary winding of UAT is equal to the main generator
voltage rating. The secondary windings can have same or
different voltages i.e. generally 11KV and or 6.9KV as
per plant layout.
|
|
132/25 KV Single Phase Traction Transformer
This transformer is installed in a traction sub-stations
along side the rail track and
is used to feed 25KV AC power
to railway electric locomotives.
The 132 KV winding is connected
to two nominated phases of incoming three phase lines
and on the secondary side, one terminal of 25 KV winding
is connected to the traction overhead equipment while
the other is solidly earthed to the running traction rails.
This transformer is designed to meet overloads
up to 200% for specified duration and dynamic/thermal
short circuit of 0.5sec and 5 sec respectively.
|