Product Introduction | Catalogues | Certificates
| Quality Assurance | Service | Clients
| Enquiry | Contact
Motor Division - Flame Proof Motors Ex (d)
The
BBL range of Flame proof Ex (d) Type "MD" motors are
from 0.37 Kw ( Frame 80) to 90 Kw ( Frame 280M). Motors are also
offered in multi speed and non standard outputs / voltages / frequencies.
FLP energy efficient motors are also available.
Download
Catalogue (432kb)
You
will need Adobe Acrobat Reader(4.0 or above) to read the Catalogue. If you do
not have it, download it here. 
These motors can be used in Zone 1 and Zone 2 areas as per IS 5572.
For further details click the links below:-
- General Application
Data for 3 Phase A.C. Motors
- Installation
and Maintenance for 3 phase Induction Motors
- Salient Features of Flame Proof Motors :
- Mechanical features : Types of construction :
Standard motors are designed for foot mounting (B3). These
are also suitable for B6, B7, B8, V5, V6 mounting without
any change.
Motors can be supplied in flange mounting (B5). These motors
will also be suitable for V1 & V3 mounting without any
change.
The flame proof motors manufactured by BBL are suitable for
ignition groups G1 to G4 as per VDE 0170/0171or Temperature
Class T1 to T4 as per IS 6381.
- Main Characteristics
Enclosure Design : The frame, end shields, terminal
boxes and bearing covers of all motors are made of grey
cast iron. The motors are so designed that the frame temperature
will remain below the ignition temperature of the gas-air
mixture.
Insulation : All motors of standard design are provided
with Class F insulation with temperature rise limited to
Class`B'.
All cast iron parts forming the flame proof enclosures are
subject to hydraulic pressure test, after final machining
as per IS : 2148
-
Cooling : All motors have bi-directional cast iron
or fabricated fans.
-
Terminal Box : Location : flame proof motors have
terminal box on the top as standard. Side terminal box can
be offered on request for frame sizes 112M & above.
-
Cable Entries : Motors for mining application (Gas
Group I ) are provided with cable entries with compound
filling sealing boxes suitable for paper insulated lead
covered double wired armoured (PILCDWA) PVC cables. Cable
entries with flameproof cable glands can also be provided
to suit PVC armoured cables. (for application in hazardous
area Gas groups IIA & IIB only.)
Motors in all frame sizes can be supplied with termination
suitable for plug & socket arrangement, against enquiry.
A cable sealing box is mandatory for all motors for use
for Gas Group. 1 & Oil Mines.